A study on copper corrosion and its effect on dielectric properties of paper oil insulation of transformers using simulation and laboratory experiments

##plugins.themes.academic_pro.article.main##

S. Daisy Flora
J. Sundara Rajan

Abstract

This study investigates the impact of copper sulphide which is formed due to corrosive sulphur in mineral oil on dielectric properties of paper oil insulation of model transformer windings. The effect of copper sulphide on electric stress distribution is explained using FEM based electric field computations. frequency domain spectroscopy and insulation resistance measurements were carried out on the prototype transformer windings under conditions of copper corrosion at different temperatures and the variations in tan δ, real and imaginary part of complex permittivity (ε’, ε”), insulation resistance, and polarization index are discussed.

##plugins.themes.academic_pro.article.details##

How to Cite
Daisy Flora, S., & Sundara Rajan, J. (2016). A study on copper corrosion and its effect on dielectric properties of paper oil insulation of transformers using simulation and laboratory experiments. Power Research - A Journal of CPRI, 151–158. Retrieved from https://cprijournal.in/index.php/pr/article/view/236

References

  1. CIGRE WG A2-32, Copper sulphide in transformer insulation, Final Report, Brochure 378, 2009.
  2. V Tumiatti, R Maina, F Scatiggio, M Pompili and R Bartnikas, Corrosive Sulphur in Mineral Oils: Its Detection and Correlated Transformer Failures, IEEE Intl. Symp. on Electrical Insulation, pp. 400-402, 2006.
  3. F Scatiggio, V Tumiatti, R Maina, M Tumiatti, M Pompili and R Bartnikas, Corrosive Sulfur in Insulating Oils:Its Detection and Correlated Power Apparatus Failures, IEEE Trans. PD, Vol. 23, No. 1, pp. 508-509, January 2008.
  4. L Lewand and S Reed, Destruction of dibenzyl disulfide in transformer oil, Doble Engineering Company, 75th Annual International Doble Conference, 2008.
  5. I Tronstad, C Marius Roel, Wilhelm Robert Glomm, Edd Anders Blekkan and MaritHelen G Ese, Ageing and Corrosion of Paper Insulated Copper Windings: The Effect of Irgamet 39 in Aged Insulated Oil, IEEE Trans. DEI, Vol. 22, No. 1, pp. 345358, February 2015.
  6. M Ramya and S Ganesan, Study of Electrical Transport Properties in Thermally Evaporated Cu2S thin films, Journal of Applied Science and Engineering, Vol. 15, No. 4, pp. 423-432, 2012.
  7. R Montes-Fernandez, V R Garcia-Colon, A Guzman Lopez, Damage assessment for transformer windings subjected to corrosive oil exposure using dielectric spectroscopy, CIGRE 2012, D1-311.
  8. G K Supramaniam, Zahrul Faizi Hussien and Mohd. Aizam, Application of Frequency Domain Spectroscopy (FDS) in Assessing Dryness and Ageing State of Transformer Insulation Systems, 2nd IEEE Intl. Conf. on Power and Energy (PECon 08), December 1-3,2008.